Chapter 2: Installation
30
Grounding the Chassis
This procedure requires these items:
Phillips head No. 2 screwdriver
10 AWG solid wire (The length of the wire will depend on your
installation.)
Crimping tool
Grounding lug (included with the chassis)
To ground the AT-CV1203 Chassis, perform the following procedure:
1. Strip the grounding wire as shown in Figure 10.
Figure 10. Stripping the Grounding Wire
2. Use a crimping tool to attach the wire to the grounding lug included
with the chassis.
Figure 11. Attaching the Grounding Wire to the Grounding Lug
11mm ±1mm
(0.44in. ±0.03in.)